if (this.Model.StructuredPageData.IsNotBlank() && (this.Model.StructuredPageData.IndexOf(availabilityKey) != -1 || this.Model.StructuredPageData.IndexOf(priceKey) != -1)) { this.Model.StructuredPageData = string.Empty; //} }

Honeywell ML6161A2009/U Non-Spring Return Damper Actuator, 24 VAC, 4 N-m, For Use With SPDT or Floating Thermostats or Building Automation Control, Plastic, Import

HONEYWELL ML6161A-2009-C ** CUSTOM PACK ** AVAILABLE IN MULTIPLES OF 20 ONLY.

Damper Actuators }

Honeywell ML6161A2009/U Non-Spring Return Damper Actuator, 24 VAC, 4 N-m, For Use With SPDT or Floating Thermostats or Building Automation Control, Plastic, Import

819527 MFG #: ML6161A-2009-C Product ID:819527
Famous Supply
  • Dimensions: 5.55 in H x 3.39 in W x 2.52 in D
  • Motor Timing: 90 s
  • Mounting Type: Direct Coupled
  • Type: Non-Spring Return
  • Voltage Rating: 24
  • Torque Rating: 4 n-m
  • Suitable For Use With: SPDT or Floating Thermostats or Building Automation Control
  • Material: Plastic
  • Domestic/Import: Import
The 35 and 70 lb-in (4 Nm and 8 Nm) Non-Spring Return Direct Coupled Actuators (DCA) are control actuators that provide floating or proportioning control for valves and dampers. The proportioning actuators accept a current or voltage signal from a controller to position the damper or valve at any chosen point between fully open and fully closed.
  • Features
  • Standards & Approvals
  • Includes
Steel plate
Selectable 45, 60 or 90 deg stroke in both clockwise (cw) or counterclockwise (ccw) directions
0 to 30 deg minimum position adjustment (cw or ccw direction) on all models
Magnetic coupling eliminates the need for mechanical stops
Two field-addable auxiliary switches
Auxiliary feedback potentiometer field-addable on select models
Manual declutch on all models
W7620 terminal unit controller compatibility
Commercial zone damper in W7600 commercial zone system compatibility
Aluminum hub, two set screws shaft adapter
Declutch mechanism manual operation
Screw terminals
Floating, SPDT, on/off control signal
90 sec at 60 Hz motor timings
cUL C22.2 No. 24-93
C-Tick N314
IEC 89/336/ECC and 73/23/EEC
Plenum Rated
UL 873
4074ENY Bag Assembly